High-precision aspirating smoke detectors for every requirement.

The complete model range for any application.

ASD 535 – perfect for large-scale applications.

The ASD 535 is the flagship model of the SecuriRAS ASD detector range.
It can monitor an area of up to 5760 square metres. Available as a single-sensor and two-sensor device, the detector analyses the airflow from one
or two sampling pipes independently. The aspirating smoke detector thus reliably spots any deviation in the airflow and detects any breakages or blockages in the sampling pipes. Up to 400 meters of sampling pipe with
a maximum of 120 sampling holes can be connected to each smoke sensor. More than 400 Pa of aspirating underpressure generates the necessary power, which means the ASD 535 has one of the most powerful fans
on the market.

The ASD 535 is available in four versions:

  • ASD 535-1 for 1 sampling tube, and 1 smoke sensor without smoke level
    indicator
  • ASD 535-2 for 2 sampling tubes, and 2 smoke sensors without smoke
    level indicator
  • ASD 535-3 for 1 sampling tube, and 1 smoke sensor with smoke level indicator
  • ASD 535-4 for 2 sampling tubes, and 2 smoke sensors with smoke level
    indicator

ASD 532 – powerful and compact.

The SecuriRAS ASD 532 is used for reliable monitoring of small and medium-sized areas and premises. It has the same technical specifications as the ASD 535, but with just one sampling pipe and a more compact fan. Anyone familiar with the ASD 535 will find added monitoring using the ASD 532 a breeze. Configuration and maintenance of the detector are made in the same
simple way.

Aesthetically, the ASD 532 is very subtle and discreet – just like all devices in the SecuriRAS ASD range. Once installed in hollow spaces, the sampling pipes are completely invisible, while the flush-mounted sampling
holes are often imperceptible. The installation is carried out with the highest possible level of adaptation to the surroundings in question. The sampling pipe can be laid out asymmetrically, which means it blends seamlessly
into the structure of the building. This eliminates the need for long sampling pipes and thus reduces costs.

ASD 531 – small and simple.

The ASD 531 is small, yet extremely powerful. As with the two larger models in the SecuriRAS ASD range, it is also equipped with the tried-and-tested HD detector with LVSC (large-volume smoke chamber). Its outstanding
sensitivity ensures high levels of safety, combined with an impressively long service life. The ASD 531 ignores individual disruptive factors effectively thanks to its patented lint filter.

The ASD 531 is the perfect choice for anyone wanting to put a smaller system into operation quickly and easily without the need for extra training. Configuration is made directly on the device using BasiConfig in just
three simple steps without the need for a PC. Operation of the compact device is just as easy. With the ASD 531, you can monitor your rooms and premises reliably and precisely with a minimum of effort and exceptional cost efficiency.

Overview of SecuriRAS ASD aspirating smoke detectors.

Mode

ASD 535

ASD 533

ASD 532

ASD 531

Channels

1/2

1

1

1

Smoke sensor

High-sensitivity smoke sensor with high-power LED, LVSC smoke chamber and patented lint filter

Monitoring area

5760 m2

1920 m2

1280 m2

720 m2

Direct integration in SecuriFire fire detection system

Yes, with XLM-35 module (alarm, pre-signal, faults, day/night sensitivity switching, reset etc.)

Smoke level indicator

Optional (version -3
and -4)

No

Series

No

Programming (PC tool)

ASD Config

ASD Config

ASD Config

Not available

Configuration

EasyConfig

EasyConfig

EasyConfig

BasicConfig

Calculation of sampling pipes

ASD PipeFlow

ASD PipeFlow

ASD PipeFlow

ASD PipeFlow

Approvals

VdS, DIBt, UL, FM, ActivFire, CCCF

VdS, UL, FM, ActivFire

VdS, UL, FM, ActivFire, CCCF

VdS, UL, FM, ActivFire, CCCF

Applications

High-bay and deepfreeze warehouses,
large data centres,
historic buildings,
large/high halls etc.

Elevator shafts,
museums, collections
of cultural artefacts,
halls, data centres,
cinemas

Elevator shafts, prison
cells, clean rooms,
laboratories, IT racks,
telecommunications
facilities etc.

Single IT racks, small
telecommunications
containers, elevator
shafts, clean rooms,
false ceilings etc.